PD3 Series Dropout Fuse Cutouts

basic information
Number:
A003
没有此类产品
Product Overview
They are connected with incoming feeder of distribution transformer or distribution line. These are primarily used to protect transformers or lines from short circuit and overloading and switching currents. The dropout fuse cutout is composed of insulator support and fuse holder, static contacts are fixed on two sides of insulator support, moving contact installed on the two ends of fuse holder, the interior of the fuse tube is arc-extinguishing tube/layer, exterior is made of phenolic compound paper tube or epoxy glass. Load break type provides stretch auxiliary contacts and arc-chute cover to switch on/off loading current.
In normal operation the fuse link is tightened to form the closed position, when fault current occurs, the fuse link melts down and electric arc produce, the arc extinguishing tube is heated and explosive gas happens. This results in high pressure inside the tube and makes tube to be disconnected from the contacts. The strength of the contact is released once the fuse elements melt down.
The cutout now is in OFF position, the operator needs to switch off the current. Use an insulated operating rod to pull, the moving contact can be pulled off. 
Dropout fuse cutouts comply with GB/T15166.3,IEC282-2,ANSI /IEEE C37.41, C37.42 standards.
 
General Working Conditions
Operating site:outdoor
Ambient temperature:-25℃ ~ 50℃
Air humidity:≤95%
Altitude:≤2000m
Mounting angle:Approximately 15º~25 º (vertical)
Product parameters
 

PD3 Series Dropout Fuse Cutouts

 
Model Rated voltage
(KV)
Rated current
(A)
Interrupting
Current (A)
Lightning
Impulse
voltage (KV)
Withstand
voltage
(KV/1min)
Leakage distance
(mm)
Appr. Weight
(kgs)
Appr. Dimensions
(cm)
PD3-15 10(15) 100 10000 125 45 350 8.3 40x33x11
200 12500 8.6
PD3-27 22(24) 100 8000 150 65 530 10.7 48x37x12
200 9600 11.1
PD3-38 33(35) 100 6000 170 75 720 13.5 60x37x12
200 8000 14.0


Note:Leakage distance of porcelain insulators is available from 220mm ~ 1000mm as requested such as 320, 400, 530, 720MM etc;
also brown color for insulator is optional.

PD3-F Series Dropout Fuse Cutouts
PD2-F Series Dropout Fuse Cutouts